Elevator / Sump Pit

Step 1
In sealing strip, apply one coat of Xypex Concentrate at the rate of 1.5 lb./sq. yd. (0.8 kg/m2), then fill slot to surface with Xypex Concentrate in Dry-Pac form.

Step 2
Apply one slurry coat of Xypex Concentrate to walls and floor slab at a rate of 1.25 - 1.5 lb./sq. yd. (0.65 - 0.8 kg/m2). After the Concentrate has set but while it is still “green”, apply a coat of Xypex Modified at the rate of 1.25 - 1.5 lb./sq. yd. (0.65 - 0.8 kg/m2).

For hydraulic elevators, please contact your Xypex representative for detail drawings.

Note 1: Schematic diagram shows Xypex application details only and does not depict standard requirements for waterstops or expansion joint sealants.

Note 2: Schematic drawing shows Xypex Coating application. Specifier may consider the alternative use of Xypex Dry Shake (DS-Series) or Xypex Additive (Admix C-Series), where applicable.

Refer to Standard Specifications for more information.